Short answer: Split it into layers connected by queues: a southbound driver (RS-485 Modbus RTU client polling devices on a schedule), a data model that maps device registers to named, scaled values with timestamps and quality flags, and a northbound client (MQTT over TLS publishing values and receiving commands), plus configuration, buffering for offline periods, diagnostics and secure updates. Each side runs independently so a slow cloud connection never stalls field-bus polling.

Architecture

[Modbus devices] --RS-485--> [Modbus RTU poller] --queue--> [Data model / mapping] --queue--> [MQTT client] --TLS--> [Broker]
                                   ^                                  |                              |
                           [Config: register map, poll rates]   [Store-and-forward buffer]   [Command handler → write queue]

Design points to discuss

  1. Configuration-driven mapping: a table per device: address, function code, register, data type (int16/uint32/float, word order), scale, units, poll period, MQTT topic. No code changes for a new device type.
  2. Scheduling: poll fast-changing values often and others rarely; respect inter-frame delays and timeouts; one outstanding request at a time per RS-485 bus.
  3. Error handling: retries with limits, mark values as stale/bad quality after timeouts, per-device health statistics, bus recovery.
  4. Buffering: store-and-forward in RAM/flash when the uplink is down, with a bounded size and a drop policy (oldest first) and timestamps from an RTC/NTP.
  5. Commands (writes): validate topic, range and permissions before writing to devices; send acknowledgements back over MQTT.
  6. Publishing efficiency: publish on change or with deadband, batch values into one JSON/CBOR/Protobuf message, use QoS 1 for important data.
  7. Security: TLS with per-device certificates, minimum broker permissions, signed firmware updates, no default passwords on a local web UI.
  8. Observability: logs, counters (polls, timeouts, CRC errors, publish failures), a status topic and a last-will message.
  9. Platform: an MCU with an RTOS for simple gateways, or embedded Linux (more protocols, containers, easier TLS and storage) for larger ones.

Interviewers are looking for: decoupling with queues, explicit handling of failure and backlog, configuration over hard-coding, and security from the start.